Product Type
Geothermal Heat Pump AHU
Nominal Capacity (BTU/h)
60000
Nominal Cooling (BTU/h)
54500
Nominal Heating (BTU/h)
56000
Blower Diameter x Width (inch)
10-63/64 x 10-43/64
Fan Motor (HP)
3/4
Refrigerant Connection Size (O.D. inch)
3/8 - 7/8
Expansion Device
Thermal Expansion Valve
Decibels dB(A)/High Speed
68
Voltage-Phase-Hz
208/230-1-60
Minimum Circuit Ampacity
5.7
Max. Overcurrent Protection
15
Air Filter Size
20" x 22"
Unit Dimensions D x W x H (in.)
24 x 22 x 54-1/2
Unit D x W x H (in.)(with pallet and packaging)
27-11/16 x 24-11/16 x 60-5/8
Indoor Coil Net face area-sq.ft.
5.99
Indoor Coil Tube diameter
9/32"
Indoor Coil No.of rows / Fins per inch
5 / 17
Shipping Weight (lbs)
194
Operating Weight (lbs)
161
- Premium efficiency – Up to 20.5 SEER, up to 10.5 HSPF
- All aluminum evaporator coil for superior corrosion resistance
- Constant torque multi-speed ECM blower motor - designed for two stage operation
- Easy to install – compatible with most standard 24 VAC heat pump thermostats
- Factory-installed TXV metering
- Multi-position Installation - upflow or horizontal right standard; field convertible to horizontal left or downflow
- Multiple electrical entry locations
- Dual front panel design for ease of maintenance
- Blower and coil easy slide out for ease of maintenance
- Fully-insulated cabinet design
- Horizontal and vertical condensate drain pans standard
- Condensate drain pan is polymer with UVC inhibitor
- Factory-sealed cabinet certified to achieve 2% or less air leakage rate at 1.0 inch water column
- Integrated filter rack with tool-less door access
- AHRI and ETL Listed